BWU2651ASi Digital Input Module, IP67, M12, 8I
Product description
ASi Digital Input Module in IP67, with 8 x M12 sockets, 8 digital inputs, Y wiring, input voltage/sensor supply out of ASi, periphery connection via 8 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 2 AB addresses
The substructure moduleis not included in the scope of delivery.
Technical data
Inputs digital | 8 |
Outputs digital | no digital outputs |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of ASi |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | no output voltage |
Connection | 8 x M12 sockets, 5 poles |
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | no |
ASi address
Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted. | 2 AB addresses |