BWU4411ASi-5 Safety Muting Module, IP67, M12, 2SI/8I/O

  • Cost-effective muting application with ASi-5 Safety. Save on module and wiring costs.
  • Safe and standard signals under only one ASi-5 address.
  • All signals for cross muting or sequential muting in one module
  • Certified muting building blocks, automatic configuration via ASIMON360 software
  • Logo_ASi-5
  • Logo_cULus
  • Logo_CE

Product description

ASi-5 Safety Muting Module in IP67, with 8 x M12 sockets, 1 x 2 channel safe input (SIL 3, cat. 4) for 1 x OSSD and 2 x 1 channel safe inputs (SIL 3, cat. 4) for 2 x Muting sensors, up to 8 digital inputs, up to 8 digital outputs, Y wiring, input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, periphery connection via 8 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 ASi-5 address
The substructure module is not included in the scope of delivery.

Technical data

Inputs Safety, SIL 3, Cat. 4

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.

1 x 2 channels + 2 x 1 channel
Safety signal inputs OSSDs
Outputs Safety, SIL 3, cat. 4 no local safe output
Safety signal outputs no Safety signal outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of AUX
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address
Special function muting

The product has earned the following certifications: