BWU2615ASi-3 PROFIsafe via PROFIBUS Gateway with integrated Safety Monitor, 2 ASi masters

Product description

ASi-3 PROFIsafe via PROFIBUS Gateway with integrated Safety Monitor, 2 ASi masters, 1 power supply for 2 ASi networks, 4 digital inputs, expandable to max. 62 x 2 channels safe inputs, 4 release circuits (2 x relay outputs and 2 x electronic safe outputs), expandable to max. 16 safe outputs, PROFIsafe (F-CPU), diagnostic and configuration via Ethernet diagnostic interface, duplicate address recognition, ASi fault detector, programming in C optional, IP20

Technical data

Fieldbus interface

Communication interface between fieldbus and gateway:

interfaces for standardized fieldbus systems in industrial automation. Bihl+Wiedemann offers a wide range of gateways for common fieldbus interfaces:

 

  • PROFIBUS
  • PROFINET
  • EtherNet/IP+ Modbus TCP
  • BACnet/IP
  • DeviceNet
  • ControlLogix
  • Compact-/MicroLogix
  • EtherCat
  • POWERLINK
  • CC-Link
  • CANopen
  • RS 485 Modbus
  • OPC UA server

 

PROFIBUS
ASi-5/ASi-3

The device communicates via the standard ASi-3 and/or ASi-5.

ASi-3 compatible
Number of ASi networks, number of ASi Master
Standard devices

"Single Master":

1 ASi network, 1 ASi-5/ASi-3 Master.

1 ASi network, 1 ASi-3 Master.

"Double Master":

2 ASi networks, 2 ASi-5/ASi-3 Masters.

2 ASi networks, 2 ASi-3 Masters.

Safety devices

"Single Master" :

1 ASi network, 1 ASi-5/ASi-3 Master.

1 ASi network, 1 ASi-3 Master.

"Double Master" :

2 ASi networks, 2 ASi-5/ASi-3 Masters.

2 ASi networks, 2 ASi-3 Masters.

"Optional ASi Safety coupling circuit" :
2 ASi networks, 1 ASi-3 Master.

2 ASi networks, 2 ASi-3 Masters
Integrated decoupling, ASi current measurement in the gateway

" yes, max. 4 A/ASi network ":

Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).

Operation with short cable lengths with standard 24 V power supply possible.


" yes, max. 8 A/ASi network ":

Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).

Operation with short cable lengths with standard 24 V power supply possible.


"yes, optimized for 2 x NEC class 2 power supplies"

Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.


"no, max. 8 A/ASi network, redundant supply ":

1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies.

Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.


" no, max. 8 A/ASi network ":

1 ASi power supply per ASi network.

yes, max. 4 A/ASi network
Inputs Safety, SIL 3, Cat. 4

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.

no local safe inputs
Outputs Safety, SIL 3, cat. 4 4 release circuits, 2 x relay, 2 x electronic safe outputs
Safety communication PROFIsafe (F-CPU)

How to troubleshoot an existing ASi installation

Manuals

    Device Description Files (GSD, EDS, ESI, SDD, etc.)

    The product has earned the following certifications: