AS-i Tuner, AS-i Bus Termination

 

 

See also:

 

 

 

 

 

AS-i Tuner:

Triplication of the AS-i cable length

 

Strengthen of the robustness of AS-i

 

Supervise the quality of the installation

 

Tool for the service

 

AS-i Bus Termination:

Doubling of the AS-i cable length

(Default value of the AS-i Tuner)

 

 

AS-i-Bus Termination
(Default value of the AS-i Tuner)

AS-i Tuner

 

 

 

Article no.: BWU1843: AS-i Diagnostic Tuner (with AS-i Slave address)

Article no.: BWU1648: AS-i Tuner (without AS-i Slave address)

Article no.: BWU1644: AS-i Bus Termination (Default value of the AS-i Tuner)

The primary task of the AS-i Tuner consists in the length adjustment in AS-i circuits without repeater.

The AS-i Diagnostic Tuner is suitable for the employment as diagnose unit, which announces the bus function of the control online. Unlike to the AS-i Tuner the AS-i Diagnostic Tuner is able to read in the traffic light announcements for each individual slave and to refer to the superordinate control system.

The result can be intergrated into an application program. It signals whether an optimization succeeded. Gradual changing of the quality of the AS-i circuit can be recognized and repaired so on time.

The AS-i Diagnostic Tuner can be switched off over a switch completely or set on a default value.

 

Article No.

BWU1648/BWU1843

BWU1644

 

Slave Profile (BWU1843)

I/O Code: 0x7

ID Code: 0xA

ID1 Code: 0x0

ID2 Code: 0x5

VENDOR ID: 0x0002

PRODUCT ID: 0x0002

AB-Slave (up to 62 Slaves)

 

Bit Allocation

In 0, In 1 binary bits, freely usable

In 2, In 3 serial communication

Out 0, Out 1 serial communication

Out 2 binary bits, freely usable

 

Connection

AS-i flat cable/AS-i round cable

Operating value

AS-i (30 V DC)

Operating current

60 mA

10 mA

LEDs

5

2

LED green

LED (AS-i Power) on:
U AS-i > 26 V
LED (AS-i Power) flashing:
18,5 V < U AS-i < 26 V

U AS-i > 26 V

LED red

Error (AS-i Analyser)

-

LED yellow

Warning (AS-i Analyser)

U AS-i > 18,5 V

LED green

Communcation o.k.

(AS-i Analyser)

-

Ambient operating temperature

0 ... +55 °C

Storage temperature

-25 ... +75 °C

Protection category according to EN 60 529

IP65

Electromagnetic sust.

according to slave spezification

EMC

EN 61 000-6-2, EN 61 000-6-3

Dimensions (L / B / H in mm)

90 / 80 / 43

46 / 19

 

The passive bus termination permits a circuit extension up to approximately 200 m

 

The Bihl+Wiedemann tuner permit a stable communication with net lengths to approximately 300 m without the employment of a Repeater and without a second power supply unit.

 

Combi Slave Profile

The AS-i Diagnostic Tuner operates after the new "combi slave profile" S-7.A.5, in which digital and serial data will be parallel transferred.

2I/1O data for the basic function of the tuner are transmitted thereby as usual, and are usable with each master. The serial data - here the analog values of the tension and the traffic light values of the individual slaves - are transmitted by the piece with the remaining bits, built up in the master again and sent from here than simple complete telegram to the control. The user finds the up-to-date measured AS-i tension and the minimum AS-i tension as 16 bit analog value in the field of the input data (similar to the analog value transmission).

So that data transmission rates of approx. 50 Baud are attainable in the AS-i A/B operation. Because of the ID code "A" is the Diagnostic Tuner a slave with an extended address range and takes in the A/B operation one of 62 addresses, in the standard mode as A-slave one of 31.

AS-i 3.0 Specification

Since the Diagnostic Tuner uses the extended functions as slave, he must be used together with a master after the AS i 3.0 specification. The primary tuner functions is available however also with a AS-i Master according to the specification 2.0 or 2.1.

Description of the Bit Allocation

 

In0, In1

The LEDs indicate the result of the optimization:

Bit

LED

Description

11

red

serious disturbances

10

yellow

more frequent replications, which should be clarified depending upon application

01

green

almost repetition-free communication

00

---

none result available (,Tuning-Phase", or the push-button even pressed)

Out2

A change of 0 to 1 has the same effect as a depressing the key. However no training procedure is released. It can be released only by means of parameters.

Parameter

The parameter bits release (independently of the position of the rotary switch) a training procedure. Only the parameter 5, then the parameter 2 within 5 seconds causes the start of a training procedure.

Analog Channel 0

Tension

as 16 bit value of 0 ... 32 767 in mV

Resolution

10 bit

Analog Channel 1

Tension

as 16 bit value of 0 ... 32 767 in mV

Resolution

10 bit

Vendor Specific Object 1

This object contains a pair of bits, which shows the condition of the slaves in this address for all 62 possible slaves:

Bit

LED

 

11

red

 

10

yellow

 

01

green

 

00

no slave

 

Byte

27

26

25

24

23

22

21

20

1

3/3A

3/3A

2/2A

2/2A

1/1A

1/1A

---

---

2

7/7A

7/7A

6/6A

6/6A

5/5A

5/5A

4/4A

4/4A

...

...

16

31B

31B

30B

30B

29B

29B

28B

28B

 

Accessories:

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Phone: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de