AS-i 3.0 Function and EMC-Test Master

 

 

See also:

 

 

 
AS-i-Master
 

Suitable for SAP4, SAP5, A2SI and ASI4U

 

For programming, developing and
tests of AS-i Slaves

 

AS-i specification 3.0

 

 

 

 

Article no. BWU1728 with Master RS 232

The AS-i Function and EMC-Test Master with RS 232 interface can be operated in 3 different modes:

1. As a standard AS-i Master according to specification 3.0.

2. As a tool for programming of the AS-i Slave ICs SAP4, SAP5, A2SI and ASI4U. This can be done with the help of Windows programs.

3. As a means to perform function and EMC tests which are necessary for every development of an AS-i slave (EMC test mode).

The AS-i Function and EMC-Test Master is used among others for the AS-i certification in Leipzig for release and test of AS-i Slaves.

 

Graphical display

Art. no. BWU1728

 

The EMC-Test Mode

It is possible to put the Master into a state that is not AS-i compliant. This option can be useful for specific tests on AS-i under laboratory conditions (e. g. tests with bursts on the lines or tests with very long wires).

By putting the AS-i Master into the EMC Test Mode it becomes an AS-i test set-up for experts.

In the test mode, the list of addressed slaves and the telegrams for contacting these slaves are given by the host. Also, it is possible to decide from within the host whether faulty answered telegrams from the AS-i Master may be repeated or not (Note: in regular AS-i operation, data telegrams can be repeated one time). As above, there are two error counters. However, in this mode the first one counts all telegrams while the second counts all faulty telegrams.

The AS-i_EMC.EXE program is designed for the operation of the AS-i Master in the EMC test mode. This program is also delivered as program for Windows.

Operating current

Master power supply
approx. 200 mA out of AS-i circuit

Operating voltage

AS-i voltage 30 V DC

Baud rates

19200 Baud

Serial interface

RS 232

AS-i cycle time

150 μs*(number of slaves + 2)

Displays

 

LCD

displaying slave addresses, error messages

LED green (power)

power on

LED green (ser active)

serial interface active

LED red (config error)

configuration error

LED green (U AS-i)

AS-i voltage OK

LED green (AS-i active)

AS-i normal operation active

LED green (prg enable)

automatic address programming enabled

LED yellow (prj mode)

the master in configuration mode

Buttons

4

Voltage of insulation

≥ 500 V

EMC directions

EN 61000-6-2, EN 61000-6-4

Ambient operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Housing

AS-i master housing in stainless steel

Dimensions (L, W, H)

120 mm, 75 mm, 83 mm

Protection category (DIN 40050)

IP20

Tolerable loading reffering to impacts and vibrations

according to EN 61 131-2

Weight

460 g

 

Individual software:

It is, of course, possible to operate the AS-i Master from other hosts with individual software. The neccessary telegrams are described in the manual.

 

Scope of delivery:

 

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Tel.: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de

Internet: http://www.bihl-wiedemann.de