AS-i 3.0 SAP4/5, ASI, ASI4U
Programming and Test Tool

 

 

See also:

 

 

 

 
AS-i 3.0 SAP4, SAP5, A2SI and ASI4U
Programming and Test Tool
For programming,
developing and
testing of AS-i Slaves
AS-i Specification 3.0

 

 

Article no. BW1783: Compact PCI Board
Article no. BW2061: PCI Board with RS 232

The AS-i 3.0 Programming and Test Tool can be operated in 3 different modes:

The EMC-Test Mode

It is possible to put the Master into a state that is not AS-i compliant. This option can be useful for specific tests on AS-i under laboratory conditions (e. g. tests with bursts on the lines or tests with very long wires).

 

By putting the AS-i Master into the EMC Test Mode it becomes an AS-i test set-up for experts.

In the test mode, the list of addressed slaves and the telegrams for contacting these slaves are given by the host. Also, it is possible to decide from within the host whether faulty answered telegrams from the AS-i Master may be repeated or not (Note: in regular AS-i operation, data telegrams can be repeated one time). As above, there are two error counters. However, in this mode the first one counts all telegrams while the second counts all faulty telegrams.

The AS-i_EMC.EXE program is designed for the operation of the AS-i Master in the EMC test mode. This program is also delivered as program for Windows.

Individual software

It is, of course, possible to operate the AS-i Master from other hosts with individual software. The neccessary telegrams are described in the manual.

Technical data
BW1783
BW2061
 
Requirements:

Compact PCI System

Compact PCI Board

 

Accessories:

AS-i Control Tools

DLL drivers for: Win NT 4.0, Win 2000, Win XP

OPC Server

Type

Compact PCI Board

PCI Board

Interfaces

32-bit PCI bus interface, 3,3 V/5 V
galvanic isolation to AS-i
AS-i circuit 1
AS-i circuit 2

 

-

RS 232

Program memory (EEPROM)

4 kb

Operating voltage

3,3 V/5 V DC and AS-i voltage

Operating current

ca. 300 mA out of 5 V power supply

ca. 100 mA out of 3,3 V power supply

ca. 70 mA out of AS-i per AS-i circuit

Voltage of insulation

≥ 500 V

EMC

according EN 61 000-6-2, EN 61 000-6-4

Ambient operating temperature

0°C .. +55°C

Storage temperature

-25°C .. +70°C

AS-i cycle time per AS-i circuit

150 μs*(Number of slaves + 2)

AS-i Specification

3.0

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Phone: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de