AS-i 8I/8O / 16I/16O Module

 

 

 

See also:

 

 

 

AS-i 8I/8O OEM Module

2 4I/4O Single Slaves

 

AS-i 3.0 8I/8O OEM Module

2 4I/4O-AB Slaves

 

AS-i 16I/16O OEM Module

4 4I/4O Single Slaves

 

AS-i 3.0 16I/16O OEM Module

4 4I/4O-AB Slaves

 

BW1898, BW1899

BW1900, BW1901

 

 
 

 

Article no. BW1898 AS-i 8I/8O OEM Module, 2 4I/4O Single Slaves

Article no. BW1899 AS-i 3.0 8I/8O OEM Module, 2 4I/4O-AB Slaves

Article no. BW1900 AS-i 16I/16O OEM Module, 4 4I/4O Single Slaves

Article no. BW1901 AS-i 3.0 16I/16O OEM Module, 4 4I/4O-AB Slaves

The AS-i Special Slave is realized by 2 resp. 4 AS-i slaves. The board is completely powered by AS-i.

A watchdog function is integrated. It powers the outputs off, if bus communication is interrupted (master failure).

The inputs/outputs can head for up to 8 resp. 16 LEDs. The energy is supplied by the AS-i system.

The addressing of 2 resp. 4 AS-i slaves is very easy with the help of 2 resp. 4 addressing sockets.

The extended addressing (AB-technique: up to 62 slaves, Single Slaves: up to 31 slaves) is possible.

Customer-specific special orders are possible on short notice. The circuit board dimensions and the plug connections can be changed as well.

Article no.

BW1898

BW1899

BW1900

BW1901

 

Programming

(Bit-setting)

 

Data bit

(Input via AS-i)

Bit function
D0 input I1/output O1
D1 input I2/output O2
D2 input I3/output O3
D3 input I4/output O4

 

Parameter bit BW1898, BW1900

Bit function
P0 not used
P1 not used
P2 not used
P3 not used

 

Parameter bit BW1899, BW1901

Bit function

P0 0 = off/1 = on (watchdog)
P1 0 = on/1 = off (data input filter 128 s)
P2 0 = on/1 = off (synchronous data I/O mode)

P3 not used

 

Programming:

Address preset 0

changeable via bus master or programming devices

 

AS-i Spec. 2.1 3.0

IO code 7 7
ID code F A
ID1 code (F) 7 (fixed)
ID2 code E 7

AS-i Specification

AS-i 2.1

AS-i 3.0

AS-i 2.1

AS-i 3.0

Extended addressing

≤ 31 slaves

≤ 62 slaves

≤ 31 slaves

≤ 62 slaves

Addressing

2 slaves

2 slaves

4 slaves

4 slaves

Connection

wiring pins

Connection

circuit board installation

Quiescent current
(input = 0, output = 0)

≤ 40 mA

≤ 50 mA

Switching threshold of inputs

≤ 0,3 mA (low)
≥ 2 mA (high)

U

20 .. 30 V DC

Outputs

8

16

Inputs

8

16

Loading capacity

70 mA per output (sum of all outputs < 200 mA)
24 V DC, no inductive load, no short circuit

Length of connector cables

I/O: max. 1,5 m

Operating voltage

via AS-i

Operating current

≤ 400 mA

≤ 500 mA

EMC directions

EN 61000-6-2, EN 61000-6-4

Ambint operating temperature

-25°C .. +70°C

Storage temperature

-40°C .. +70°C

Protection category EN 60 529

IP00

Allowable shock and vibration stress

≤ 15 g, T ≤ 11 ms
10 .. 55 Hz, 0,5 mm amplitude

Dimensions (L / W / H in mm)

104 / 41 / 16

93 / 51 / 16

 

 

 

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Tel.: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de

Internet: http://www.bihl-wiedemann.de