AS-i Module to control damper actuators
|
|
|
See also:
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AS-i Module for controlling damper actuators
and for detection the damper position
Runtime monitoring of the damper motor in master possible
Connection by external flat cable terminal via insulation penetration technology
AS-i Specifications 2.1/3.0
|
|
|
Article no. BW2028: Supplied by AS-i
|
The AS-i module to control damper actuators meets the requirements of the AS-i Specifications 2.1/3.0. It is used to control the damper actuator and detect the damper position damper open and damper close as well as the intermediate position ,damper opens" or ,damper closes". In addition external contact can be requested, e.g. of an smoke detector or an temperature switch.
The connections are short-circuit -and overload protected. A watchdog function, which switches the outputs to their currentless switching state if there is no communication on the AS-i circuit, is integrated. The transfer function is permanent monitored in the integrated AS-i Slave and in the AS-i Master.
This module can be connected via cage clamp terminals or ready to plug via Belimo-compatible connector.
|
Article no.
|
BW2028
|
|
Programming (Bit-setting)
Data bit (input via AS-i)
Bit Function
D0 Input I1 (damper closed)
D1 Input I2 (damper open)
D2 Input I3 (external contackt)
D3 Input I4 (reserved)
D0 Output O1 (damper open up)
D1 Output O2 (reserved)
Parameter bit
Bit Function
Bit P3:
1: Peripheral fault is indicated
0: Peripheral fault is not indicated
Bit P1, P2 :
not used
Programming:
preset: address 0
changeable via busmaster-programming devices
Accessories:
-
Connecting cable 40 cm with M12 plug
(art. no. BW2065)
-
AS-i passive distributor, AS-i flat cable on M12 (art. no. BW1239)
-
AS-i passive distributor, AS-i/24 V on M12 (art. no. BW1976)
|
|
Connections
|
|
Damper actuator
|
cage clamp terminals or
Belimo-compatible connectors
|
|
AS-i
|
cage clamp terminals
|
|
Properties
|
|
Achievement
|
4 inputs / 2 outputs
|
|
Output function
|
transistor PNP
|
|
Operating voltage
|
26,5 ... 31,6 VDC
|
|
Quiescent current
(Inputs = 0, Outputs = 0)
|
≤ 20 mA
|
|
Max. current consumption incl. motor
|
≤ 420 mA
|
|
Short-circuit proof
|
yes
|
|
Protective circuit of inputs
|
DC PNP
|
|
Sensor supply
|
by AS-i
|
|
Voltage range
|
18 ... 30 VDC
|
|
Switching threshold of inputs
|
≤ 0,8 mA (low); ≥ 5 mA (high)
|
|
U
|
18 ... 30 VDC
|
|
Loading capacity
|
400 mA per output
(sum of all outputs ≤ 400 mA) out of AS-i
|
|
I/O configuration
|
7
|
|
ID code
|
D
|
|
Displays
|
|
Operating
|
LED green
|
|
Function
|
LED yellow
|
|
Inputs 1 - 4
|
4 x LEDs yellow
|
|
Outputs 1 - 2
|
2 x LEDs yellow
|
|
Standard conformity
|
|
EMC
|
EN 61 000-6-2, EN 61 000-6-3, EN 61 000-6-4
|
|
AS-i profile
|
S 7. D
|
|
Housing
|
|
Operating temperature
|
-25°C ... +60°C
|
|
Storage temperature
|
-40°C ... +70°C
|
|
Protection category
|
IP 54
|
|
Housing
|
synthetic material
|
|
Dimensions (L / W / H in mm)
|
160 / 90 / 55
|
|
|
Terminal connections:
|
|
|
|
X1
|
X2
|
|
X5
|
|
1
|
AS-i +
|
In 3
|
|
In 4
|
|
2
|
AS-i -
|
+24 V
|
|
+24 V
|
|
3
|
|
In 2
|
S6
|
|
|
4
|
|
+24 V
|
S4
|
|
|
5
|
|
In 1
|
S2
|
|
|
6
|
|
+24 V
|
S1
|
|
|
7
|
|
In 4
|
|
|
|
8
|
|
+24 V
|
|
|
|
9
|
|
Out 1
|
2
|
|
|
10
|
|
0 V
|
1
|
|
|
11
|
|
Out 2
|
|
|
|
12
|
|
0 V
|
|
|
Bihl+Wiedemann GmbH
Floßwörthstr. 41
D-68199 Mannheim
Phone: (+49) 621 / 339 96-0
Fax: (+49) 621 / 339 22 39
eMail: mail@bihl-wiedemann.de