AS-i Module for
building services engineering

 

 

See also:

 

 

 

 

 

 

AS-i I/O Modules
 

AS-i Specification 3.0

 

Single Slave (up to 31 slaves) or
AB Slave (up to 62 slaves)

 

Housing with external fastening tabs

 

 

 

 

Article no. BW2137: 4 inputs/4 outputs, AS-i AB Slave

Article no. BW2138: 4 outputs, AS-i Single Slave

Article no. BW2139: 4 inputs/3 outputs, AS-i AB Slave

Article no. BW2175: 4 inputs/4 outputs, AS-i Single Slave

Article no. BW2466: 4 inputs, AS-i Single Slave

The AS-i 4I/4O Module, which meets the requirements of the new AS-i Specification 3.0 is the board based solution for an AS-i slave with 4 inputs and 4 outputs.

The inputs and outputs are powered out of separated 24V. They are short circuit and overload protected and can each be loaded with up to 500mA (outputs). If bus communication is interrupted (master failure), the outputs are switched to their currentless switching state by the watchdog. Connection by spring-type terminals. Installation by external fastening tabs.

 

Article no.

BW2137

BW2138

BW2139

BW2175

BW2466

 

Programming

(Bit setting)

 

Data bit

(Input via AS-i)

Bit Function
D0 Input I1/Output O1
D1 Input I2/Output O2
D2 Input I3/Output O3
D3 Input I4/Output O4

 

Parameter bit

Bit Function

P0 0 = Off/1 = On (watchdog)

P1 0 = On/1 = Off (data input filter 128 s)

P2 0 = On/1 = Off (synchronous I/O mode)

P3 not used

 

Programming:

adress preset0
changeable via bus master or programming devices

 

 
 

Connection

cage clamp terminals

Quiescent current
(Input = 0, Output = 0)

≤ 20mA

U

20 ... 30V DC

Outputs (elektronic)

4

3

4

-

Inputs (elektronic)

4

-

4

Capacity

500mA per output from 24V supply

Length of connector cables

I/O: max. 15 m

AS-i Profil

S-7.A.7

S-8.F.E

S-7.A.E

S-7.DF.E

S-7.A.7

IO-Code

7

8

7

ID-Code

A

F

A

F

ID1-Code

7 (fixed)

F (default)

7 (default)

F (default)

ID2-Code

7

E

Operating voltage

via AS-i

Operating current

≤ 70mA

Displays

LED green (AS-i)

LED on: voltage at the AS-i clamp
LED flashing: error, e.g. slave on adress 0
(default setting) or peripheral fault

LED red (Fault)

LED on:AS-i communication error
LED flashing: AS-i peripheral fault, e.g. no 24V
or short circuit at an output, fuse

LED green (AUX)

LED on: 24V available
LED off: absence 24V

EMC directions

EN 61 000-6-2
EN 61 000-6-4

Operating temperature

-25°C ... +70°C

Storage temperature

-40°C ... +70°C

Protection category EN 60 529

IP54

Allowable shock and vibration stress

≤ 15 g, T ≤ 11 ms
10 ... 55 Hz, 0,5 mm amplitude

Housing material

polycarbonate / polystyrene

Dimensions (L / B / H in mm)

93 / 93 / 55

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Phone: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de