Article
no.
|
BW2137
|
BW2138
|
BW2139
|
BW2175
|
BW2466
|
|
Programming
(Bit
setting)
Data
bit
(Input
via AS-i)
Bit
Function
D0 Input I1/Output O1
D1 Input I2/Output O2
D2 Input I3/Output O3
D3 Input I4/Output O4
Parameter
bit
Bit
Function
P0
0 = Off/1 = On (watchdog)
P1
0 = On/1 = Off (data input filter 128 s)
P2
0 = On/1 = Off (synchronous I/O mode)
P3
not used
Programming:
adress
preset0
changeable via bus master or programming devices
|
|
Connection
|
cage
clamp terminals
|
|
Quiescent
current
(Input = 0, Output = 0)
|
≤
20mA
|
|
U
|
20
... 30V DC
|
|
Outputs
(elektronic)
|
4
|
3
|
4
|
-
|
|
Inputs
(elektronic)
|
4
|
-
|
4
|
|
Capacity
|
500mA
per output from 24V supply
|
|
Length
of connector cables
|
I/O:
max. 15 m
|
|
AS-i
Profil
|
S-7.A.7
|
S-8.F.E
|
S-7.A.E
|
S-7.DF.E
|
S-7.A.7
|
|
IO-Code
|
7
|
8
|
7
|
|
ID-Code
|
A
|
F
|
A
|
F
|
|
ID1-Code
|
7
(fixed)
|
F
(default)
|
7
(default)
|
F
(default)
|
|
ID2-Code
|
7
|
E
|
|
Operating
voltage
|
via
AS-i
|
|
Operating
current
|
≤
70mA
|
|
Displays
|
|
LED green (AS-i)
|
LED
on: voltage at the AS-i clamp
LED flashing: error, e.g. slave on adress 0
(default setting) or peripheral fault
|
|
LED red (Fault)
|
LED
on:AS-i communication error
LED flashing: AS-i peripheral fault, e.g. no 24V
or short circuit at an output, fuse
|
|
LED green (AUX)
|
LED
on: 24V available
LED off: absence 24V
|
|
EMC
directions
|
EN
61 000-6-2
EN 61 000-6-4
|
|
Operating
temperature
|
-25°C
... +70°C
|
|
Storage
temperature
|
-40°C
... +70°C
|
|
Protection
category EN 60 529
|
IP54
|
|
Allowable
shock and vibration stress
|
≤
15 g, T ≤ 11 ms
10 ... 55 Hz, 0,5 mm amplitude
|
|
Housing
material
|
polycarbonate
/ polystyrene
|
|
Dimensions
(L / B / H in mm)
|
93
/ 93 / 55
|