AS-i Counter Module

 

 

See also:

 

 

 

 

A/B inputs
 

Profile 7.3 ,Plug and Play"
as simple as digital AS-i I/O

 

High protection category IP65

 

 

 

 

 

Article no. BWU2218: Counter Module 2-channel input

Article no. BWU2219: Counter Module 2 x 2-channel input

Article no. BWU2189: Counter Module 4 x 2-channel input

The AS-i Counter Module has inputs for standard sensors (24 V, pnp, push-pull). The module counts the impulses with the two channels (BWU2218), twice two channels (BWU2219) or 4 x two channels (BWU2189) up- and downwards and outputs the result as 16 bit value (-32768 ... 32767) via AS-i. The start value is -30768.

With the help of parameters the module can be set to zero as well as the counting direction can be defined. Es stehen verschiedene Different pre-divisors are available, which can be select via AS-i parameters as well.

As long as the AS-i parameter for setting zero is set the counting is stopped. After the setting to zero of the counting value a pre-divisor or the AS-i parameter for no pre-divisor must be adjusted again.

The module reports a peripheral fault at counter overflow (underflow).

 

Article no.

BWU2218

BWU2219

BWU2189

Inputs

1 M12 input (2 channels)

2 M12 inputs (2 x 2 channels)

4 M12 inputs (4 x 2 channels)

Voltage supply, sensors

via AS-i

Range of value

-32 768 ... 32 767 dec. (start value: -30768)

Counting rate

max. 20 kHz

Power supply sensor

max: 150 mA

AS-i profile

7.3

ID code

3hex

ID2 code

Chex

Dhex

E

IO code

7hex

Displays

LEDs geen (In 1 - 4)

state of input 1

state of inputs 1 and 2

state of inputs 1, 2, 3 and 4

LED green (PWR)

AS-i voltage

LED red (FAULT)

AS-i communication error, peripheral fault

Operating current

< 200 mA

Operating voltage

AS-i (30 VDC)

Voltage of insulation

≥ 500 V

EMV

EN 61 000-6-2
EN 61 000-6-4

Ambient operating temperature

0°C ... +70°C

Storage temperature

-25°C ... +85°C

Housing

housing for DIN-rail mounting

Dimensions (L / W / H in mm)

90 / 80 / 43

Protection category DIN 40 050

housing IP65

 

 

 

Programming (Bit-setting of AS-i parameters)

 

BWU2218

Bit P0

Parameter

 

Bit P1

Parameter

 

Bit P3

Bit P2

Parameter

1

count upwards In 1

1

counter In 1

1

1

no pre-divisor

0

count downwards In 1

0

set zero In 1

1

0

pre-divisor = 2

 

 

0

1

pre-divisor = 8

0

0

pre-divisor = 32

BWU2219

Bit P0

Parameter

 

Bit P1

Parameter

 

Bit P2

Parameter

 

Bit P3

Parameter

1

count upwards In 1

1

counter In 1

1

count upwards In 2

1

counter In 2

0

count downwards In 1

0

set zero In 1

0

count downwards In 2

0

set zero In 2

Start value:
At power-up, all the counter with 0x87D0 (-30768) are initialized to indicate that there is no zero-setting.

 

Accessories:

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Phone: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de