Article no
|
BW2255
|
Input
|
|
Nominal input voltage
|
100 - 240 VAC, 47 - 63 Hz
|
|
Input voltage
|
94 - 265 VAC
|
|
Nominal input current
|
0,65 A at 230 VAC; 1,0 A bei 115 VAC
|
|
Peak inrush current
|
It < 1,5 As
|
|
Power factor cos ϕ
|
0,4 capacitive at 230 VAC; 0,55 capacitive at 115 VAC
|
|
Applicable wire size of input clamps
|
0,5 ... 2,5 mm (AWG20 ... AWG13)
|
|
Tightening torque of the input clamps
|
0,6 - 0,8 Nm
|
|
Insulation stripping lentgh
|
10 mm
|
Output
|
|
Output voltage Uout
|
31,2V ± 3%
|
|
Output current Iout
|
0 - 1,8 A
|
|
Ripple
|
< 50 mVpp (0 ... 10 kHz); < 10 mVpp (35 ... 500 kHz)
|
|
Current limitation typ.
|
2,3 A
|
|
Efficiency typ.
|
88%
|
|
Applicable wire size of output clamps
|
0,5 ... 2,5 mm (AWG20 ... AWG13)
|
|
Tightening torque of the output clamps
|
0,6 - 0,8 Nm
|
|
Insulation stripping lentgh
|
10 mm
|
Regulation
|
|
Line regulation
|
< 0,2% at Uin = 230 VAC ± 15%
|
|
Load regulation
|
< 0,5% at 0 A → 1,8 A
|
|
Dynamics
|
< 2 ms at 10 ↔ 90% (Iout max), peaks < 2%
|
Protection and monitoring
|
|
Internal fuse
|
T2,5 A / 250 V TR5 IEC 60 127-3/IV
|
|
Current limitation
|
Protected against continuous short circuit (see diagram)
|
|
Overload protection
|
yes
|
|
Idle running protection
|
yes
|
|
Hold-up time
|
> 65 ms bei Uin = 230 VAC; > 10 ms bei Uin = 115 VAC
|
Safety
|
VDE 0805/EN 60 950/IEC 950
|
|
Output
|
Safety extra low voltage SELV
|
|
Protective system (EN 60 529)
|
Class II
|
|
Protection category
|
IP20
|
|
Leakage current
|
< 0,25 mA (47 - 63 Hz line frequency)
|
EMV CE-certified
|
EN 55 011, EN 50 082-1, EN 61 000-6-2
|
|
RFI suppression
|
EN 55 022, EN 55 011 class B
|
|
Static discharge ESD ref. (IEC 61 000-4-2)
|
8 kV contact discharge, 15 kV free air discharge (EN 61 000-4-2)
|
|
Electromagnetic fields ref. (IEC 61 000-4-3)
|
10 V/m (EN 61 000-4-3)
|
|
Burst ref.( IEC 61 000-4-4)
|
4 kV input, 2kV output/capacitive coupling clamp (EN 61 000-4-4)
|
|
Surge ref. (IEC 61 000-4-5)
|
4 kV unsymmetrical (EN 61 000-4-5)
|
|
Conducted disturbances ref. (IEC 61 000-4-6)
|
10V, 150 kHz ... 80 MHz (EN 61 000-4-6)
|
AS-i Certification
|
|
|
AS-i Certification
|
Pending
|
Operational data
|
|
Temperature range
|
-10°C ... +40°C, by free convection (start from -25°C)
|
|
Power derating
|
2,5% / K from +40°C (see diagram)
|
|
Storage temperature
|
-25°C ... +85°C
|
Displays
|
|
LED green
|
The green LED indicates normal operation (0 A ... 1,8 A)
|
Mounting
|
|
Mounting position
|
vertikal as shown in figure
|
|
Input terminals
|
upper side
|
|
Output terminals
|
lower side
|
Assembly
|
Plastic slider for fastening to mounting rails DIN EN 50 022-35
|
Mechanics
|
|
Dimensions max. (W / H / D):
|
45 / 72 / 105
|
|
Weight
|
approx. 0,2 kg
|