AS-i Repeater IP20

 


Circuit Extension by 100 m

On-Board Diagnostics AS-i Fault

Galvanic isolation

Requires no programming

Passive on the AS-i network
(no slave address required)

Simple mounting beside the AS-i power supply




Article no. BWU1460 (Circuit extension by 100 m)

The AS-i Repeater with On-Board Diagnostics have got a LED for power supply and AS-i communication errors. The red AS-i Fault LED flashes as long as there is no AS-i communication. The communication error LED will help the customer to find basic installation problems really fast.
The new AS-i Repeaters are compatible with all existing AS-i Repeaters.
Especially the AS-i Repeaters in IP20 can be easily mounted into the switchboard in combination with an AS-i power supply.
Together with the AS-i Tuner and the AS-i Bus Termination, the AS-i Repeater from Bihl+Wiedemann is a perfect package for every AS-i network.

Connections
Combicon clamps
Operating voltage
via AS-i
Operating current
60 mA (per network segment), 120 mA (total)
Quantity of needed AS-i power supplies
1
4 LEDs

PWR1
AS-i power network 1
FAULT1
AS-i communication error network 1
PWR2
AS-i power network 2
FAULT2
AS-i communication error network 2
Ambient operating temperature
0 … +55 °C
Storage temperature
-25 … +75 °C
Protection category according to EN 60 529
IP20
Electromagnetic sustainability
according to slave specification
Voltage of insulation
> 500 V
EMC
according to EN61000-6-3, EN61000-6-2
Dimensions (L, W, H) 105 mm, 22,5 mm, 114 mm


Note: The AS-i Repeater does not occupy any slave address. The total amount of the slaves (31 respectively 62) per AS-i network remains constant. No programming required.



Connections BWU1460
1
n.c.
2
n.c.
3
AS-i-2
4
AS-i+2
5
n.c.


20
n.c.
21
AS-i+1
22
AS-i-1
23
n.c.
24
n.c.