AS-i 3.0 PROFIBUS Gateway,
PROFIsafe for 1 AS-i network

 

See also:

 

 

 

PROFIsafe for 1 AS-i network

 

  • Redundant power supply out of AS-i:
    all fundamental functions of the device remain available even in case of
    power failure in one of the two AS-i networks
  • AS-i-Safety input slaves report via PROFIsafe
  • AS-i-Safety output slaves switch via PROFIsafe
1 AS-i 3.0 Single Master, PROFIBUS-Slave
  • Full functional range
    of Bihl+Wiedemann PROFIBUS Gateway BWU1567!
  • Compatible with the wide range of
    Bihl+Wiedemann power supplies

Safe AS-i outputs are supported on both AS-i networks

  • Multiple safe AS-i outputs possible via a single AS-i address

Chip card for storage of configuration data

 

 

 

Article number

BWU2433

PROFIBUS interface

according to DIN 19 245, part 3

Baud rates

9,6 kBaud up to 12 000 kBaud, automatic recognition

DP functions

imaging of the AS-i slaves as I/O data of the PROFIBUS
complete diagnosis and configuration via the PROFIBUS DP

Serial interface

RS 232

AS-i cycle time

150 μs * (number of slaves + 2)

Card slot

chip card for storage of configuration data

Displays

LCD

indication of slave addresses and error messages

LED power

power on

LED PROFIBUS

PROFIBUS master recognized

LED config error

configuration error

LED U AS-i

AS-i voltage OK

LED AS-i active

AS-i normal operation active

LED prg enable

automatic addresses programming enabled

LED prj mode

configuration mode active

Electrical data

Operating current

master power supply,
max. 300 mA out of AS-i circuit 1 (approx. 70 mA ... 300 mA),
max. 300 mA out of AS-i circuit 2 (approx. 70 mA ... 300 mA);
in sum max. 370 mA

Operating voltage

30 V, 9 W

Voltage of insulation

≥ 500 V

UL-specifications (UL508)

External Protection

An isolated source with a secondary open circuit voltage of ≤ 30 VDC
with a 3 A maximum over current protection.
Over current protection is not required when a Class 2 source is employed.

in general

UL mark does not provide UL certification for any functional safety rating
or aspects of the above devices.

cTÜVus

The devices BWU2433 from Bihl + Wiedemann GmbH were safety certified
by TÜV Rheinland of North America, Inc. according to UL-standards
and meet the safety requierements for the North American market.

Standards

EN 50 295
EN 61 000-6-2
EN 61 000-6-4
EN 954-1:1996, category 4
EN 62 061:2005, SIL 3
EN 61 508:2006, SIL 3
EN ISO 13 849-1:2008, performance level e
EN ISO 13 849-2:2008

Housing

AS-i master housing in stainless steel

Ambient operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Dimensions (L / W / H in mm)

120 / 100 / 96

Protection category IEC 60 529

IP20

Tolerable loading referring to impacts and vibrations

according to EN 61 131-2

Weight

800 g

 

 

Accessories:

 

Bihl+Wiedemann GmbH

Floßwörthstr. 41

D-68199 Mannheim

Phone: (+49) 621 / 339 96-0

Fax: (+49) 621 / 339 22 39

eMail: mail@bihl-wiedemann.de