BWU3144ASi Digital I/O Module EXTREME, IP67, M12, 4I/4O
Product description
ASi Digital I/O Module EXTREME Product Line in IP67, with 8 x M12 sockets, 4 digital inputs, 4 digital outputs, Y wiring, input voltage/sensor supply out of ASi, output voltage/actuator supply out of AUX, periphery connection via 8 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 AB address
100% protection against moisture
High resistance to salt spray
High corrosion resistance to chemically active substances
Assured functionality at extreme temperatures from – 40 °C to 70 °C
Shock resistant to 30 g (11 ms)
Vibration rated for a frequency of 5-500 Hz at an amplitude of 50 mm pp / 6 g
The substructure module is not included in the scope of delivery.
Technical data
Type | IP67, 8 x M12, EXTREME |
Housing | 8 x M12 |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP67 |
Inputs digital | 4 |
Outputs digital | 4 x electronic |
M8/M12 wiring
Single wiring: 1 input or output per connection.
Y wiring: 2 inputs or outputs per connection.
Mixed wiring: 1 input and 1 output per connection.
Exact pin assignment see data sheet. | Y |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of ASi |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX |
Connection | 8 x M12 sockets, 5 poles |
ASi connection
The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| ASi profile cable |
ASi address
AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed. | 1 AB address |