BWU4766Active Distributor ASi, IP67, 4O
Product description
Active Distributor ASi, IP67, housing depth 19 mm, 4 digital outputs, output voltage/actuator supply out of AUX, periphery connection via 1 x round cable/connecting wires, cable length 3 m, flat design, installation in cable duct possible (installation depth ≥ 19 mm), LED, connections for 1 x ASi and 1 x AUX profile cables, ASi connection via profile cable and piercing technology, 1 AB address
Technical data
Outputs digital | 4 x electronic |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX |
Connection | 1 x round cable/connecting wires |
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | 3 m |
Flat design, installation in cable duct possible
Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation. | yes, depth: 19 mm |
ASi address
AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed. | 1 AB address |