BWU2398ASi Motor Module, IP67, M12 for 24V motorized rollers, 4I/2O/2AO
Product description
ASi Motor Module in IP67, with 4 x M12 sockets for 2 x 24 V motorized rollers Interroll (EC200, EC300) or Rollex (Typ 840), 4 digital inputs, 2 digital outputs, 2 analog outputs, input voltage/sensor supply out of ASi, output voltage/actuator supply out of AUX, periphery connection via 4 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 AB address
Speed setting via ASi parameter
The motor module is designed to supply the 24 V directly to the motor. At high currents or surges as they occur for example at braking, the module will not be damaged.
The cable protection should be realized outside the motor module with additional measures.
Thesubstructure module is not included in the scope of delivery.
Technical data
Drive
"SEW MOVIMOT®": Motor module to control geared motors with frequency inverters.
"NORD": Motor module to control geared motors with frequency inverters.
Brake chopper for 24 V motorized rollers: For limiting the voltage feedback, suitable for all 24 V motorized rollers. | Interroll (EC200, EC300), Rollex (Typ 840) | ||||||||||||||||||||
Number of Drives | 2 | ||||||||||||||||||||
Inputs digital | 2 | ||||||||||||||||||||
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of ASi | ||||||||||||||||||||
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX | ||||||||||||||||||||
Connection
PUR line, oil resistant. Further connection options are available on request.
| 4 x M12 sockets, 5 poles | ||||||||||||||||||||
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | no | ||||||||||||||||||||
ASi address
AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed. | 1 AB address |