Circuit Board Modules
BWR3213ASi PCB Module, 73 mm x 37,5 mm, 4I/4O, wiring pins, straight, thick coated
Product description
ASi PCB Module, 73 mm x 37,5 mm, 4 digital inputs, 4 digital outputs, input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, max. 250 mA per output, periphery connection via wiring pins, straight, thick coated, LED, ASi connection via wiring pins, straight, 1 AB slave
Technical data
Type | circuit board 73 mm x 37,5 mm | ||||||||||||||
Circuit board dimensions
2 holes for assembly angles. | 73 mm x 37,5 mm | ||||||||||||||
Inputs Safety, SIL 3, Cat. 4 | - | ||||||||||||||
Inputs digital | 4 | ||||||||||||||
Outputs digital | 4 x electronic | ||||||||||||||
Outputs Safety, SIL 3, cat. 4 | - | ||||||||||||||
Safety signal inputs | - | ||||||||||||||
Inputs analog | - | ||||||||||||||
PCB connection
further connection options are available on request.
| wiring pins, straight | ||||||||||||||
Coating
Coating protects components and circuit boards when touched.
| thick coated | ||||||||||||||
LED status display
status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show as usual regarding the ASi Slaves- the status of the ASi Slaves. Uaux is indicated by a green LED. | yes | ||||||||||||||
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of AUX | ||||||||||||||
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential. For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX | ||||||||||||||
ASi connection
The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| wiring pin, straight | ||||||||||||||
ASi address
AB Slave (max. 62 AB Slaves/ASi network), 2 AB Slaves (max. 31 modules with 2 AB Slaves), Single Slaves (max. 31 Single Slaves/ASi network), ASi-5 Slave (max. 62 ASi-5 Slaves/ASi network), mixed use allowed. | 1 AB Slave |
General information
Commissioning
Manuals
EPLAN Macros
Video Tutorial
The product has earned the following certifications: