Archives Safety I/O Modules
BWU4209ASi-5 Safety Input Module, IP67, M12, 2SI/12I/12O
Product description
ASi-5 Safety Input Module in IP67, with 8 x M12 sockets, 2 x 2 channel safe inputs (SIL 3, cat. 4) for floating contacts, up to 12 digital inputs, up to 12 digital outputs, Y wiring, input voltage/sensor supply out of AUX, output voltage/actuator supply out of AUX, periphery connection via 8 x M12 sockets, 5 poles, ASi connection via profile cable and piercing technology, 1 ASi-5 address
The substructure module is not included in the scope of delivery.
Technical data
Type | IP67, 8 x M12, ASi-5 Safety |
Housing | 8 x M12 |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP67 |
Inputs Safety, SIL 3, Cat. 4 | 2 x 2 channels |
Inputs digital, EDM
An externally connected relay (contactor) can be monitored by connecting the feedback loop to the EDM input. | up to 12, depending on configuration |
Outputs digital | up to 12 x electronic, depending on configuration |
Safety signal inputs | floating contacts |
Input voltage (sensor supply)
inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential. | out of AUX |
Output voltage (actuator supply)
Electronic outputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, outputs shall not be connected to earth or to external potential.
For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet. | out of AUX |
Length of connector cable | unlimited |
ASi connection
The connection to ASi as well to AUX (auxiliary 24 V power) is made via yellow resp. black ASi profile cable with piercing technology or via M12 socket (in IP20 via clamps).
| ASi profile cable |
ASi address
AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed. | 1 ASi-5 address |
General information
Commissioning
Manuals
EPLAN Macros
The product has earned the following certifications: