BWU3087Passive Distributor ASi/AUX to 2 x M12 sockets, 5 poles, depth 35 mm, IP67
Product description
Passive Distributor ASi/AUX, housing depth 35 mm, IP67, connections for 1 x ASi and 1 x AUX profile cables to 2 x M12 sockets, 5 poles, internal protection via changeable 4 A slow-blow fuses for ASi and AUX, LED
with 4 changeable fuses
Technical data
Type | Passive distributor ASi/AUX |
Profile cable connection | 1 x ASi, 1 x AUX 24 V |
Connection | 2 x M12 sockets, 5 poles |
Internal fuse
"4 A, changeable": The internal protection is realized via changeable 4 A fuses (slow-blow) for ASi and/or AUX. At each connection ≤4 A are available. "1 A, self-resetting": The internal protection is realized via self-resetting 1 A fuses for ASi and/or AUX. At each connection ≤1 A are available.
"4 A, slow-blow fuse": The internal protection is realized via one 4 A slow-blow fuse for ASi and/or AUX. At each connection ≤4 A are available.
"8 A, slow-blow fuse": The internal protection is realized via one 8 A slow-blow fuse for ASi and/or AUX. At each connection ≤8 A are available.
"8 A, slow-blow fuse + 1 A, self-resetting": The internal protection is realized via one 8 A slow-blow fuse for AUX and via one self-resetting 1 A fuse for ASi. At each M8 connection (AUX) ≤6 are available, at each M8 connection (ASi) ≤1 A are available. | 4 A, changeable |
Round cable
Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled. In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted. | no |
Flat design, installation in cable duct possible
Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation. | no |
Housing | depth: 35 mm |
LED status display
status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED. | yes |
Protection rating
"IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. | IP67 |