BWU4729Passive distributor ASi/AUX, profile cable branch, depth 42 mm, IP67

Product description

Passive distributor ASi/AUX as profile cable branch, housing depth 42 mm, IP67, connections for 2 x ASi profile cable and 2 x AUX profile cable

The substructure module is not included in the scope of delivery.

Technical data

Type Passive distributor ASi/AUX
Profile cable connection 2 x ASi, 2 x AUX 24 V
Connection profile cable branch
Internal fuse

"4 A, changeable":

The internal protection is realized via changeable 4 A fuses (slow-blow) for ASi and/or AUX. At each connection ≤4 A are available.

"1 A, self-resetting":

The internal protection is realized via self-resetting 1 A fuses for ASi and/or AUX. At each connection ≤1 A are available.

 

"4 A, slow-blow fuse":

The internal protection is realized via one 4 A slow-blow fuse for ASi and/or AUX. At each connection ≤4 A are available.

 

"8 A, slow-blow fuse":

The internal protection is realized via one 8 A slow-blow fuse for ASi and/or AUX. At each connection ≤8 A are available.

 

 

"8 A, slow-blow fuse + 1 A, self-resetting":

The internal protection is realized via one 8 A slow-blow fuse for AUX and via one self-resetting 1 A fuse for ASi. At each M8 connection (AUX) ≤6 are available, at each M8 connection (ASi) ≤1 A are available.

no
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

no
Flat design, installation in cable duct possible

Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation.

no
Housing depth: 42 mm
LED status display

status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED.

no
Protection rating

"IP20":
Protected against solid foreign bodies having a diameter of 12.5 mm or larger and against finger contact, not protected against water.


"IP40":

Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water.

"IP54":

Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.


"IP65":
Dust-tight, full protection against contact, protection against spray water (jet) from any angle.

"IP67":

Dust-tight, full protection against contact, protection against temporary immersion.

IP67