BWU4379ASi Safety I/O Module, IP67, M12, 1SI/1SRO/1I

  • Safe relay output in IP67
  • Applications up to category 4/PLe/SIL3
  • Generation of safety-switched AUX branches
  • Secure data exchange of system parts with different AUX potentials

 

Product information

  • Logo_ASi-5
  • Logo_cULus
  • Logo_CE

Product description

ASi Safety I/O Module in IP67, housing 51 mm x 60 mm with 4 x M12 sockets, 1 x 2 channels safe input (SIL 3, cat. 4) for floating contacts, 1 release circuit (2 x relay outputs), 1 digital input, input voltage/sensor supply out of AUX, relais control out of ASi, periphery connection via 4 x M12 sockets and via profile cable (switched AUX) and piercing technology, 5 poles and profile, without limitation of connector cable length (loop resistance 150 Ohm), ASi/AUX connection via profile cable and piercing technology, 2 single addresses + 1 AB address

Technical data

Inputs Safety, SIL 3, Cat. 4

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.

1 x 2 channels
Safety signal inputs floating contacts
Outputs Safety, SIL 3, cat. 4 1 release circuit, 2 x relay
Safety signal outputs relay outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of AUX
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

out of ASi
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

2 Single addresses + 1 AB address
Special function safety-switched AUX branches via M12, secure data exchange

How to troubleshoot an existing ASi installation

Manuals