BWU2045ASi Safety Output Module, IP20, 1SRO/1EDM

Product description

ASi Safety Output Module in IP20, 22,5 mm x 114 mm, with 4 x 4 contacts, 1 release circuit (2 x relay outputs), 1 EDM, input voltage/sensor supply out of ASi, output voltage/actuator supply out of ASi, periphery connection via Push-in terminals, length of connector cable max. 15 m for inputs and unlimited for outputs, ASi connection via Push-in terminals, 1 single address + 1 AB address

Technical data

Inputs Safety, SIL 3, Cat. 4

Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.

no local safe inputs
Safety signal inputs no Safety signal inputs
Outputs Safety, SIL 3, cat. 4 1 release circuit, 2 x relay
Safety signal outputs relay outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
Output voltage (actuator supply)

Electronic outputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, outputs shall not be connected to earth or to external potential.

 

For relay outputs the relay contacts are initiated from ASi. The load circuit is powered externally as specified in the data sheet.

no output voltage
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 Single address + 1 AB address
Special function no special function

How to troubleshoot an existing ASi installation