BWU2045ASi Safety Output Module, IP20, 1SRO/1EDM

Product description

ASi Safety Output Module in IP20, 22,5 mm x 114 mm, with 4 x COMBICON connections, 1 release circuit (2 x relay outputs), 1 EDM, input voltage/sensor supply out of ASi, output voltage/actuator supply out of ASi, periphery connection via clamps, length of connector cable max. 15 m for inputs and unlimited for outputs, ASi connection via clamps, 1 single address + 1 AB address

Technical data

Outputs Safety, SIL 3, cat. 4 1 release circuit, 2 x relay
Safety signal outputs relay outputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (auxiliary 24 V power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
ASi address

AB address (max. 62 AB addresses/ASi network), 2 AB addresses (max. 31 modules with 2 AB addresses), Single addresses (max. 31 Single addresses/ASi network), ASi-5 address (max. 62 ASi-5 addresses/ASi network), mixed use allowed.
For ASi modules with two ASi nodes the second Asi node is turned off as long as the first Asi node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 Single address + 1 AB address

How to troubleshoot an existing ASi installation

Manuals

    The product has earned the following certifications: