BWU4202ASi-5 Counter Module, IP67, M12

  • ASi-5 – Great data bandwidth, short cycle times
  • 4 x counter inputs, individually configurable and parameterizable
  • Transmission of 4 independent counter values within up to 1.27 ms
  • Frequencies up to 250 kHz
  • Frequency and period duration measurement with and without filtering
  • Logo_ASi-5
  • Logo_cULus
  • Logo_CE

Product description

ASi-5 Counter Module in IP67, with 4 x M12 sockets, 4 x counter inputs, pulse counter, range of value -2147483647 ... 2147483647 dec., counting rate max. 250 kHz, input voltage/sensor supply out of ASi, periphery connection via 4 x M12 sockets, 5 poles, ASi connection via M12, 1 ASi-5 address

Technical data

Inputs digital 4 x counter inputs
Input voltage (sensor supply)

inputs are supplied by ASi or by AUX (24 V or 48 V auxiliary power). If supplied by ASi, inputs shall not be connected to earth or to external potential.

out of ASi
counting rate max. 250 kHz
M8/M12 wiring

Single wiring: 1 input or output per connection.

 

Y wiring: 2 inputs or outputs per connection.

 

Mixed wiring: 1 input and 1 output per connection.

 

Exact pin assignment see data sheet.
 

Pin2 = Pulse
Connection 4 x M12 sockets, 5 poles
ASi connection

The connection to ASi and AUX (24 V auxiliary power) is made for modules in the active distributor or blue IP67 housing via the yellow or black ASi profile cable with piercing technology or via an M12 plug. Modules for the control cabinet are connected via terminals and PCB modules via wiring pins, connection wires or terminals.


Line protection: If the module is supplied via a M12 connection with A or B coding, it may only be used with a current load of max. 4 A per pin in acc. with IEC 61076-2-101 and IEC 61076-2-109. A fused tap is recommended. There is no such limitation for modules supplied via piercing contacts.

ASi via M12
ASi address

Bihl+Wiedemann offers modules with AB address, single address or ASi-5 address. In some cases, ASi modules can occupy several (different) addresses. Mixed operation of modules with different addressing in the same ASi circuit is permitted.
For ASi modules with two ASi-3 nodes, the second ASi-3 node is turned off as long as the first ASi-3 node is addressed to address "0".
Upon request, ASi modules are available with specific ASi node profiles.

1 ASi-5 address

How to troubleshoot an existing ASi installation

Manuals

    Device Description Files (GSD, EDS, ESI, SDD, etc.)