BW3074Small Starter Kit Safety Gateway in Stainless Steel

    Product description

    The Small Starter Kit Safety Gateway in Stainless Steel is available fully assembled and pre-wired in a practical case. This cost-effective starter version offers ample space for the installation of your own modules. The Small Starter Kit Safety Gateway in Stainless Steel will be assembled by default with a PROFINET Gateway with integrated Safety Monitor, but most other prevalent fieldbus systems are available on request.

    Technical data

    Fieldbus interface

    Communication interface between fieldbus and gateway:

    interfaces for standardized fieldbus systems in industrial automation. Bihl+Wiedemann offers a wide range of gateways for common fieldbus interfaces:

     

    • PROFIBUS
    • PROFINET
    • EtherNet/IP+ Modbus TCP
    • BACnet/IP
    • DeviceNet
    • ControlLogix
    • Compact-/MicroLogix
    • EtherCat
    • POWERLINK
    • CC-Link
    • CANopen
    • RS 485 Modbus
    • OPC UA server

     

    PROFINET
    ASi-5/ASi-3

    The device communicates via the standard ASi-3 and/or ASi-5.

    ASi-3 compatible
    Number of ASi networks, number of ASi Master
    Standard devices

    "Single Master":

    1 ASi network, 1 ASi-5/ASi-3 Master.

    1 ASi network, 1 ASi-3 Master.

    "Double Master":

    2 ASi networks, 2 ASi-5/ASi-3 Masters.

    2 ASi networks, 2 ASi-3 Masters.

    Safety devices

    "Single Master" :

    1 ASi network, 1 ASi-5/ASi-3 Master.

    1 ASi network, 1 ASi-3 Master.

    "Double Master" :

    2 ASi networks, 2 ASi-5/ASi-3 Masters.

    2 ASi networks, 2 ASi-3 Masters.

    "Optional ASi Safety coupling circuit" :
    2 ASi networks, 1 ASi-3 Master.

    1 ASi network, 1 ASi-3 Master
    Integrated decoupling, ASi current measurement in the gateway

    " yes, max. 4 A/ASi network ":

    Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).

    Operation with short cable lengths with standard 24 V power supply possible.


    " yes, max. 8 A/ASi network ":

    Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply).

    Operation with short cable lengths with standard 24 V power supply possible.


    "yes, optimized for 2 x NEC class 2 power supplies"

    Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.


    "no, max. 8 A/ASi network, redundant supply ":

    1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies.

    Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.


    " no, max. 8 A/ASi network ":

    1 ASi power supply per ASi network.

    yes, max. 4 A/ASi network
    Inputs Safety, SIL 3, Cat. 4

    Safe inputs can be configured as 1-channel or 2-channels depending on the desired application or PL and SIL level.

    3 x 2 channels
    Outputs Safety, SIL 3, cat. 4 6 release circuits, 6 x electronic safe outputs
    Safety communication Safe Link

    How to easily implement your ASi installation

      How to troubleshoot an existing ASi installation

      Manuals