ControlLogix Fieldbus system
ControlLogix ASi Gateway
Function
The Bihl+Wiedemann ASi Master for ControlLogix of Allen-Bradley has 2 ASi masters according to the new specification. A fast and easy commissioning can be accomplished with the use of two pushbuttons and the display. ASi I/O data and status information is mapped into the PLC processor’s I/O data.
ASi Scope
Diagnostics, which go far beyond the standard diagnostics facilitate the simple detection of the occassionally occuring configuration errors and further irritations towards the ASi communication. So in case of an error the down time of machines can be minimized or you can initiate preventive maintenance.
Commissioning and monitoring
The ASi Master can be commissioned respectively programmed with the help of the software "ASi Control Tools360". Commissioning, debugging and setting up the system without the software can only be accomplished with the use of two push-buttons, the display and the LEDs directly on the system.
ControlLogix ASi
Figure | Type | Model | "IP20": "IP40": Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water. "IP54": Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.
Dust-tight, full protection against contact, protection against temporary immersion. |
Communication interface between fieldbus and gateway: interfaces for standardized fieldbus systems in industrial automation. PROFIBUS ASi gateway: interface for a PROFIBUS fieldbus
PROFIBUS ASi Basic gateway: interface for a PROFIBUS fieldbus PROFIBUS ASi IP65 gateway: interface for a PROFIBUS fieldbus EtherNet/IP+ Modbus TCP ASi gateway: interface for an EtherNet/IP+ ModbusTCP fieldbus BACnet/IP ASi gateway: interface for a BACnet/IP fieldbus Compact-/MicroLogix ASi gateway: interface for the Compact-/MicroLogix fieldbus POWERLINK ASi gateway: interface for an POWERLINK fieldbus OPC UA server: interface for the OPC UA communication
| Standard devices"Single Master": 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. Safety devices "Single Master" : 1 ASi network, 1 ASi-5/ASi-3 Master. 1 ASi network, 1 ASi-3 Master. 2 ASi networks, 2 ASi-5/ASi-3 Masters. 2 ASi networks, 2 ASi-3 Masters. | " yes, max. 4 A/ASi network ": Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Cost-effective power for 2 ASi networks with 1 power supply (optionally supply of multiple Single Gateways by 1 power supply). Operation with short cable lengths with standard 24 V power supply possible.
Data decoupling integrated in the gateway. Optimized for use with 2 x UL certified 30 V/3 A power supplies with power limitation <100 W (BW4223). In combination 2 separate NEC Class 2 compliant ASi circuits are created.
1 ASi power supply per ASi network. Gateway is powered in normal operation from one of the two ASi power supplies. Should one ASi power supply fail, switching to the other ASi power supply allows all the diagnostics functions to be maintained and the unaffected ASi network continues to operate.
1 ASi power supply per ASi network. | "USB": Access to ASi Master and Safety Monitor with Bihl+Wiedemann proprietary software by using the USB interface. Access to ASi Master and Safety Monitor with Bihl+Wiedemann software by using the Ethernet diagnostic interface or Ethernet fieldbus interface. Access to ASi Master and Safety Monitor with Bihl+Wiedemann software by using the Ethernet diagnostic interface. Access to ASi Master and Safety Monitor with Bihl+Wiedemann software by using the Ethernet fieldbus interface or by using an adapter cable via RS 232 interface.
Access to ASi Master and Safety Monitor with Bihl+Wiedemann software by using an adapter cable via RS 232 interface.
The latest version of the device description file of the gateway/gateway with integrated safety monitor (GSD, GSDML, EDS, etc.) is available in the "Downloads" section of the respective device. | Detects whether the same address has been assigned to two ASi nodes. Frequent error when using a handheld addressing device. | Checks the ASi line for interference effects such as noise, external voltages, ... | Using a C-program offers the possibility to run mini-PLC functions with a gateway. | Article No. |
---|---|---|---|---|---|---|---|---|---|---|---|
![]() | ControlLogix ASi | Gateway | IP20 | ControlLogix | 2 ASi networks, 2 ASi-3 Masters | no, max. 8 A/ASi network | RS 232 | no | no | no | BWU1488 ASi-3 Master/Scanner A-B ControlLogix, 2 masters |
![]() | ControlLogix ASi | Gateway | IP20 | complete set ControlLogix | 2 ASi networks, 2 ASi-3 Masters | no, max. 8 A/ASi network | RS 232 | no | no | no | BW4724 ASi-3 Master/Scanner A-B ControlLogix, complete set, 2 masters |