BWU4912Passive Distributor AUX to 1 x M12 power cable socket, straight, L-coded, 4 poles, depth 25 mm, IP67

Product description

Passive Distributor AUX, housing depth 25 mm, IP67, connections for 2 x AUX profile cables (galvanically separated) to 1 x M12 power cable socket, straight, L-coded, 4 poles, cable length 1 m, flat design, installation in cable duct possible (installation depth ≥25 mm)

Technical data

Type Passive distributor AUX
Profile cable connection 1 x AUX 24 V, 1 x AUX 48 V
Connection

PUR line, oil resistant. Further connection options are available on request.

      M12 socket M12 cable socket, angled  M12 cable socket, straight   M8 cable socket, straight   round cable/connecting wires     profile cable branch          push in terminals
       2 x round cables/connecting wires 2,5 mm²

1 x M12 power cable socket, straight, L-coded, 4 poles
Internal fuse

"4 A, changeable":

The internal protection is realized via changeable 4 A fuses (slow-blow) for ASi and/or AUX. At each connection ≤4 A are available.

"1 A, self-resetting":

The internal protection is realized via self-resetting 1 A fuses for ASi and/or AUX. At each connection ≤1 A are available.

 

"4 A, slow-blow fuse":

The internal protection is realized via one 4 A slow-blow fuse for ASi and/or AUX. At each connection ≤4 A are available.

 

"8 A, slow-blow fuse":

The internal protection is realized via one 8 A slow-blow fuse for ASi and/or AUX. At each connection ≤8 A are available.

 

 

"8 A, slow-blow fuse + 1 A, self-resetting":

The internal protection is realized via one 8 A slow-blow fuse for AUX and via one self-resetting 1 A fuse for ASi. At each M8 connection (AUX) ≤6 are available, at each M8 connection (ASi) ≤1 A are available.

no
Round cable

Under normal conditions (no bus termination or repeater), the permissible total length of the ASi segment is max. 100 m. The calculation should take into consideration that the length of the connection cable (round cable) for each connected passive distributor must be doubled.

In the case of the active distributors (ASi modules) however only the one ASi profile cable is counted.

1 m
Flat design, installation in cable duct possible

Modules with a flat housing design and with cables which exit the sides make these ideal for installation in cable ducts, cable channels, cable troughs, cable rails or cable trays. Please note the respective housing depth for your particular installation.

yes, depth: 25 mm
Housing depth: 25 mm
LED status display

status of in- and outputs is indicated by LEDs. In addition to that, both ASi LEDs (PWR green and FAULT red) show - as usual regarding the ASi modules - the status of the ASi modules. Uaux is indicated by a green LED.

yes
Protection rating

"IP20":
Protected against solid foreign bodies having a diameter of 12.5 mm or larger and against finger contact, not protected against water.


"IP40":

Protected against solid foreign bodies having a diameter of 1.0 mm or larger, protected against access with a wire, no protection against water.

"IP54":

Protection against dust in damaging amounts, complete protection against contact, protection against splashing water in any angle.


"IP65":
Dust-tight, full protection against contact, protection against spray water (jet) from any angle.

"IP67":

Dust-tight, full protection against contact, protection against temporary immersion.

IP67